- -15%
Explosion Proof Sample Draw LEL Sensor Gas Detector
The Model 1017 series is a compact sample draw direct connect LEL sensor assembly with a built-in pump that accepts a 24VDC input. This unit features a watertight cast aluminum alloy housing which is rated as explosion proof for Class I, Division I, Groups B, C, & D. The Model 1017 has a detection range of 0-100% LEL and can draw a sample from 100 feet away.
- Monitors 0-100% LEL
- Sample-draw with long life internal pump
- Cast aluminum alloy housing
- Stainless steel inlet and outlet fittings with flame arrestors
- Housing and flame arrestors CSA and UL classified for use in hazardous locations Class I, Division I, Groups B, C, & D.
- Also available for oxygen monitoring, 0-25% volume
- Operates on 24VDC input
Free Shipping On All Orders (2-5 days)
30 Days Money Back & One Year Warranty
Built-in Privacy & Security Protection
The Model 1017 series is a compact sample draw direct connect LEL sensor assembly with a built-in pump that accepts a 24VDC input. This unit features a watertight cast aluminum alloy housing rated as explosion-proof for Class I, Division I, Groups B, C, & D. The Model 1017 has a detection range of 0-100% LEL and can draw a sample from 100 feet away.
The Model 1017 can interface to any RKI Beacon 110, 200, 410, or M2 controllers, Beacon 800, Riken Kieki, or third-party control system utilizing an optional amplifier with a 4-20 mA feedback signal. The stainless steel inlet and exhaust fittings on the bottom of the housing allow the gas sample to enter and exit. This is a cost-effective way to monitor LEL with a sample draw direct connect sensor.
Specifications
Target Gas |
Combustible gas, methane calibration standard (oxygen detection version also available) |
Input Power |
24 VDC |
Construction (housing) |
Cast aluminum alloy, watertight, explosion proof, NEMA 4, 7, 9 |
Housing Approval |
CSA and UL classified for use in hazardous locations Class I, Division I, Groups B, C, & D. |
Location |
Indoor or outdoor use |
Temperature |
32 to 104° F (0 to 40 C) |
Dimensions |
7.00 in. H x 7.00 in.W x 6.13 in. D |
Sampling Method |
Sample draw pump |
Recommended Sample Flow |
1.0 LPM |
Detection Range |
0 to 100% LEL, (optionally 0-25% volume oxygen) |
Response Time |
90% in 30 seconds |
Accuracy |
±5% of reading or ± 2% LEL (whichever is greater) |
Warranty |
One year material and workmanship |